2.5MW 10kV Transformer-Isolated Containerized Energy Storage Power Conversion System

Product Summary
2.5MW 10kV Containerized Energy Storage Power Conversion System. This containerized power conversion unit provides 2500kW rated DC-side power across a 1000–1500V operating voltage range and a 2500kVA AC-side interface rated at 10kV. Transformer isolation, battery communication and dispatch ...
Basic Properties
Place of Origin: China
Brand Name: Voltertech
Certification: IEC62477-1 , IEC61000-6/2/4 , UN3536
Model Number: BESS-25MW-W
Trading Properties
Minimum Order Quantity: 1 Unit
Price: Negotiable
Payment Terms: L/C,T/T,Western Union
Supply Ability: 5000 Units per Month
Product Description

2.5MW 10kV Containerized Energy Storage Power Conversion System.

This containerized power conversion unit provides 2500kW rated DC-side power across a 1000–1500V operating voltage range and a 2500kVA AC-side interface rated at 10kV. Transformer isolation, battery communication and dispatch communication interfaces are specified for integration within an energy storage project.

Check the Main Electrical Interfaces First

For a MW-class energy storage project, selecting the power conversion equipment begins with electrical compatibility rather than battery energy capacity alone. The battery-side DC voltage, required conversion power and AC grid interface all need to match the project architecture.

Rated Power
2500kW
Check against the required power conversion capacity of the project.
DC Interface
1000–1500V
The battery-side DC architecture should operate within the specified voltage range.
AC Interface
10kV
The AC side is designed around a 10kV medium-voltage interface.
Isolation
Transformer
Transformer isolation is specified on the AC side.

2.5MW Power Conversion Between High-Voltage DC and 10kV AC

The DC side is rated at 2500kW with a maximum current of 2619A. On the AC side, rated output power is specified at 2500kVA with a rated voltage of 10kV.

The specified AC-side power factor is adjustable from -1 to +1, while maximum total harmonic distortion is listed as no more than 3% at rated power.

The technical parameter sheet does not specify battery energy capacity in kWh. The product is therefore presented according to its 2.5MW power conversion and 10kV grid-interface specifications rather than as a fixed-MWh battery energy storage system.

Core Technical Specifications

Swipe left or right to view the full specification table.

Section Parameter Specification
DC Side Operating Voltage Range 1000–1500V
DC Side Rated Output Power 2500kW
DC Side Maximum Current 2619A
AC Side Rated Output Power 2500kVA
AC Side Rated AC Voltage 10kV
AC Side Rated AC Current 145A
AC Side Isolation Mode Transformer Isolation
AC Side Total Harmonic Distortion ≤3% at Rated Power
AC Side Power Factor -1 to +1 Adjustable
System Cooling Mode Air Cooling
System Operating Temperature -25°C to +50°C
System Storage Temperature -25°C to +55°C
System Operating Relative Humidity 0% – 95%
System Working Altitude ≤2000m
System Dimensions 5523 × 2400 × 2800mm
System Net Weight Approx. 15T

Communication Interfaces for System Integration

The specification separates battery-side communication from dispatch communication, allowing the power conversion unit to exchange information with compatible battery equipment and project-level control systems.

Battery Communication CAN / RS485
Dispatch Communication Modbus RTU / Modbus TCP / IEC 60870-5-104

Container Size Matters at 2.5MW

Electrical compatibility is only one part of project selection. The physical container measures 5523 × 2400 × 2800mm and has an approximate net weight of 15 tonnes.

These values should be considered when planning the available installation area and equipment handling requirements. The specified operating temperature range is -25°C to +50°C, with a working altitude of up to 2000m.

Air-Cooled Power Conversion Configuration

Air cooling is specified as the cooling method for this configuration. Although the source document carries a general liquid-cooling product heading, the individual technical parameter for this model explicitly lists air cooling.

Frequently Asked Questions

Is a 2.5MW 10kV energy storage PCS suitable for my project?

Suitability depends on the required conversion power, battery-side DC voltage and AC grid connection. This configuration is rated at 2500kW on the DC side, operates within a 1000–1500V DC range and provides a 10kV AC interface. These values should be checked against the electrical architecture of the project.

Can this 2.5MW energy storage system connect directly to a 10kV network?

The AC side is specified at 2500kVA with a rated voltage of 10kV and transformer isolation. Final connection design should still be confirmed according to the project's grid requirements and electrical design.

What battery voltage is required for a 2.5MW energy storage PCS?

The specified DC operating voltage range is 1000V to 1500V, with a maximum DC current of 2619A. The battery system should be configured so that its operating voltage remains within these limits.

Does this 2.5MW system include batteries and a fixed MWh capacity?

The technical parameter sheet does not specify a fixed battery capacity in kWh or MWh. This product is defined by its power conversion, DC input and 10kV AC-side parameters, so the battery configuration should be confirmed separately according to the project requirements.

Can the 2.5MW PCS communicate with an EMS or power dispatch system?

Yes. Dispatch communication interfaces include Modbus RTU, Modbus TCP and IEC 60870-5-104. Battery-side communication interfaces include CAN and RS485. Final compatibility should be checked against the project's control platform.

How do I choose between 1.25MW, 1.725MW and 2.5MW energy storage PCS configurations?

The main difference is rated power capacity. The appropriate configuration should be selected according to the project's required power, battery DC architecture, 10kV AC-side requirements, installation space and overall system design rather than choosing by power rating alone.

What space and site conditions are required for the 2.5MW container?

The equipment dimensions are 5523 × 2400 × 2800mm with an approximate net weight of 15 tonnes. The specified operating temperature range is -25°C to +50°C and the working altitude is up to 2000m. These values should be considered during site planning.

What information should I send when requesting a 2.5MW energy storage solution?

Provide the required system power, battery-side DC voltage range, AC grid voltage, communication requirements, site temperature, altitude and available installation space. If the battery system has already been selected, its DC voltage and current information should also be provided for compatibility checking.

Check Whether the 2.5MW Power Block Matches Your Project

Provide your required power, battery-side DC voltage, AC grid voltage, communication requirements and site conditions. The 2.5MW / 10kV configuration can then be evaluated against your project parameters.

Discuss Your 2.5MW Energy Storage Project
Product Details
Highlight:

2.5MW Energy Storage Power Conversion System

,

10kV Containerized Energy Storage System

,

Transformer-Isolated Power Conversion Unit

System Function: MW-Class Energy Storage Power Conversion
Electrical Position: AC-Side Conversion & Grid Interface
Grid Connection Class: 10kV Medium-Voltage Interface
Battery-Side Architecture: 1000–1500V High-Voltage DC
Isolation Design: Transformer-Isolated
Installation Format: Containerized Power Equipment
Control Integration: Battery & Dispatch Communication
Project Buyer: EPC / System Integrator / Energy Contractor

Customer Service

Related Products
  • 30kWh 15kVA Air Cooling Commercial Energy Storage System with LiFePO4 Battery

    30kWh 15kVA Air Cooling Commercial Energy Storage System with LiFePO4 Battery The Voltertech commercial energy storage system is designed for small-scale commercial and industrial (C&I) solar projects, providing reliable battery storage, backup power and energy management solutions for businesses, ...
  • 11.52kWh 3.6kW Stackable Battery Energy Storage System All In One

    11.52kWh 3.6kW All in One Energy Storage System with Stackable Battery Design This all in one energy storage system combines an 11.52kWh stackable LiFePO4 battery bank with a 3.6kW inverter, MPPT solar charging and two AC output channels. It offers a larger energy reserve for projects that need ...
  • 15.36kWh 12kW All In One Energy Storage System Dual MPPT Stackable Battery Storage

    15.36kWh 12kW All in One Energy Storage System with Dual MPPT Input This all in one energy storage system combines a 15.36kWh LiFePO4 battery, 12kW pure sine wave inverter, dual MPPT solar charging and local monitoring in one floor-standing structure. It offers a practical starting configuration for ...
Send An Inquiry