30kWh 15kVA Commercial BESS with STS: Commercial Battery Energy Storage System for Backup Load Planning

Product Summary
Voltertech 30kWh LiFePO4 commercial BESS with 15kVA rated AC output, STS function and 16.5kVA maximum off-grid output. Air-cooled IP54 cabinet with LAN/RS485/CAN interfaces for small commercial backup load planning.
Basic Properties
Place of Origin: China
Brand Name: Voltertech
Certification: IEC62477-1 , IEC61000-6/2/4 , UN3536
Model Number: BESS-30KWH-15KW-W-3
Trading Properties
Minimum Order Quantity: 1 Unit
Price: Negotiable
Payment Terms: L/C,T/T,Western Union
Supply Ability: 5000 Units per Month
Product Description

30kWh 15kVA Commercial BESS with STS for Backup Load Planning

For a small business, choosing battery storage is not simply about how many kilowatt-hours are available. The electrical loads that must remain powered, their operating priorities and the required switching arrangement are equally important.

The Voltertech BESS-30KWH-15KW-W is a 30kWh LiFePO4 commercial battery energy storage system with 15kVA rated AC output, STS functionality and air cooling. Designed for small commercial power projects, it provides a cabinet-based solution for installers planning battery backup, electrical load management and compatible hybrid energy systems.

Identify Essential Loads Before Selecting Battery Storage

A retail shop, office or small commercial facility may have different electrical priorities during a power interruption. Security equipment, communication systems, selected lighting and operational equipment should be evaluated according to their power requirements and interruption tolerance.

Installers should prepare a load schedule showing the rated power, simultaneous demand and expected operating duration of the circuits requiring backup.

The 30kWh battery provides nominal stored energy, while the available backup duration depends on usable capacity, conversion losses and the actual connected loads.

15kVA Rated Output and Off-Grid Load Requirements

The system specifies 15kVA rated AC output for both grid-connected and off-grid operation, with a maximum off-grid output rating of 16.5kVA.

These values should be considered when evaluating commercial electrical loads. The rated apparent power in kVA is not automatically equivalent to active power in kW, and the maximum off-grid output must not be assumed to be available continuously.

Motor starting demand, load power factor and the manufacturer's approved operating limits should be checked before confirming the final application.

STS Function for Power Transfer Planning

The BESS specification includes an STS function for supported power transfer arrangements. This is relevant when engineers need to coordinate different power sources and operating modes within a commercial electrical system.

The exact switching sequence, transfer time and load compatibility should be confirmed using the approved system documentation. STS functionality alone does not guarantee uninterrupted power to sensitive electrical equipment.

For circuits requiring continuous power, the project engineer should evaluate whether additional UPS protection is necessary.

Optional Solar PV Integration

The system can be configured with optional PV input through two channels, each specified for up to 15kW of solar input power. This allows installers to consider solar generation as part of the broader energy storage configuration.

PV equipment inclusion must be confirmed before ordering. Where solar input is selected, module string voltage, current and operating conditions must comply with the applicable inverter specifications.

Cabinet Installation and Communication

The air-cooled battery cabinet has an IP54 protection rating, measures 802 × 1028 × 1890mm and weighs approximately 700kg. Installers should provide suitable handling arrangements, electrical clearances and access for air circulation and maintenance.

LAN, RS485 and CAN communication interfaces support integration planning with compatible monitoring and control equipment. Actual protocol availability and monitoring functions should be verified during system commissioning.

Technical Specifications

Parameter Specification
Battery Energy 30kWh
Rated AC Output 15kVA (On-Grid / Off-Grid)
Maximum Off-Grid Output 16.5kVA
Battery Chemistry / Nominal Voltage LiFePO4 / 307.2V
AC Voltage / Frequency 230/400V / 50/60Hz
STS Function Supported
Cycle Life 6,000 Cycles
Cooling / Protection Air Cooling / IP54
Communication LAN / RS485 / CAN
Dimensions / Net Weight 802 × 1028 × 1890mm / Approx. 700kg

Suitable Small Commercial Projects

This 30kWh commercial BESS can be evaluated for retail premises, small offices, business service facilities and selected workshop backup applications.

For each project, the installer should confirm the required backup circuits, available electrical supply, load characteristics and expected operating conditions. Final suitability depends on the complete energy storage system configuration.

Frequently Asked Questions

1. How should a business select which loads receive battery backup?

The project engineer should identify essential circuits, calculate simultaneous demand and determine the required backup duration. Loads with high starting current or sensitive power requirements need additional assessment.

2. Does 15kVA mean the system provides 15kW continuously?

Not necessarily. kVA represents apparent power, while kW represents active power. The relationship depends on power factor and the approved PCS operating specifications.

3. Is the 16.5kVA maximum off-grid output available continuously?

The supplied specification lists 16.5kVA as maximum off-grid output. Its permitted operating duration and load conditions should be verified before using this rating for system design.

4. Can the STS function provide uninterrupted backup for computers?

The system includes STS functionality, but the transfer time and specific operating behavior are not defined in the available parameter sheet. Sensitive equipment may require separate UPS protection.

5. What information is needed for a commercial BESS quotation?

Please provide the site electrical voltage, load schedule, essential backup circuits, required operating duration and proposed solar PV configuration if applicable. A single-line electrical diagram will help our team review the project requirements.

Planning a 30kWh Commercial Backup Energy Storage Project?

Contact Voltertech with your business load requirements, electrical configuration and expected backup applications. Our team can discuss the available BESS configuration, technical documentation and quotation options for your project.

Request BESS Details & Quotation
Product Details
Highlight:

30kWh Commercial BESS

,

15kVA Commercial Battery Energy Storage System

,

STS Commercial Energy Storage System

Product Positioning: Small Commercial Backup Energy Storage
Target Buyers: Solar Installers / EPCs / ESS Integrators
Main Application: Retail & Small Business Backup
Load Planning: Essential / Non-Essential Circuits
Switching Design: STS-Based Transfer Planning
Electrical Integration: Commercial AC Distribution
Commissioning Focus: Load Testing & Switching Verification
Project Documents: Load Schedule / Single-Line Diagram

Customer Service

Related Products
Send An Inquiry